| Tegangan Terukur (rms) |
26kV |
26kV |
34kV |
34kV |
| Tegangan Operasi Kontinu (rms) |
20,8kV |
20,8kV |
27,2kV |
27,2kV |
| Tegangan Referensi DC (U1mA) |
≥37kV |
≥37kV |
≥48kV |
≥48kV |
| Arus Pelepasan Nominal (puncak) |
5kA |
5kA |
5kA |
5kA |
| Arus Impuls Switching (puncak) |
0,5kA |
0,5kA |
0,5kA |
0,5kA |
| Arus Referensi Frekuensi Daya (puncak) |
1mA |
1mA |
1mA |
1mA |
| Tegangan Referensi Frekuensi Daya |
≥26kV |
≥26kV |
≥34kV |
≥34kV |
| Tegangan Sisa Akibat Impuls Petir (5kA) |
≤66kV |
≤72kV |
≤85kV |
≤90kV |
| Tegangan Sisa di bawah Arus Impuls Pensaklaran |
≤56kV |
≤65kV |
≤75kV |
≤85kV |
| Tegangan Sisa di Bawah Impuls Arus Curam |
≤76kV |
≤85kV |
≤95kV |
≤105kV |
| Ketahanan Arus Gelombang Persegi Panjang 2ms |
150A |
150A |
150A |
150A |
| Kemampuan Menahan Impuls Arus Tinggi |
65kA |
65kA |
65kA |
65kA |
| Tegangan Tahan Impuls Petir pada Selubung Konektor Terlindung |
125kV |
125kV |
125kV |
125kV |
| Tegangan Tahan Frekuensi Daya (rms) dari Selubung Konektor Terlindung |
65kV |
65kV |
65kV |
65kV |